NEW QUESTION # 27
When planning horizontal cable pathways in a large commercial environment, BICSI recommends that no cross-sectional fill rate exceed what percentage for conduit containing telecommunications cabling?

  • A. 50%
  • B. 25%
  • C. 60%
  • D. 40%

Answer: D


NEW QUESTION # 28
Which tool is required to pull backbone cable of significant weight?

  • A. Tugger
  • B. Pull string
  • C. Furcating harness
  • D. Pulling eye

Answer: A


NEW QUESTION # 29
If an installed cable fails the Near-End Crosstalk (NEXT) margin requirement, which corrective action is MOST likely to fix the issue?

  • A. Shortening the total cable run by 5 m (16 ft)
  • B. Substituting a different type of RJ45 connector with the same color code
  • C. Reversing the orientation of the patch panel
  • D. Re-terminating the cable while maintaining proper pair twist up to the termination

Answer: D


NEW QUESTION # 30
What grade of plywood is recommended for use with ICT systems?

  • A. A/C
  • B. A/D
  • C. C/D
  • D. B/C

Answer: A


NEW QUESTION # 31
Which of the following combinations is used to identify the tip conductors in Pair 1 of a 4-pair cable?

  • A. White-Orange
  • B. White-Blue
  • C. Brown-White
  • D. Green-White

Answer: B


NEW QUESTION # 32
For a telecommunications grounding and bonding system, which bonding conductor is typically responsible for ensuring that all metallic pathways and equipment within a building's telecommunications spaces are at the same ground potential?

  • A. Grounding Equalizer (GE)
  • B. Equipment Bonding Jumper (EBJ)
  • C. Telecommunications Bonding Backbone (TBB)
  • D. Telecommunications Main Grounding Busbar (TMGB)

Answer: C


NEW QUESTION # 33
When routing conduits through a fire-rated floor assembly, which principle BEST ensures compliance with fire code requirements?

  • A. Oversizing the conduit to reduce cable friction
  • B. Installing a second parallel conduit for redundancy
  • C. Placing a service loop inside the conduit above the floor
  • D. Filling any gap around the conduit with an approved firestop system

Answer: D


NEW QUESTION # 34
What type of connector is used with ribbon cable?

  • A. MPO
  • B. F Connector
  • C. N Connector
  • D. Array

Answer: D


NEW QUESTION # 35
Which of the following must be measured before the length of a coaxial cable can be calculated?

  • A. Delay skew
  • B. Propagation delay
  • C. DC loop resistance
  • D. Insertion loss

Answer: C


NEW QUESTION # 36
You are pre-terminating cable. Where should the labels be placed?

  • A. Far end
  • B. Both ends
  • C. Near end

Answer: B


NEW QUESTION # 37
Which of the following describes a situation where a BICSI Installer 2 may have to calculate a cable's derating factor?

  • A. When running cables in environments below -20°C (-4°F)
  • B. When running cable vertically without any horizontal transitions
  • C. When bundling large numbers of cables together, impacting heat dissipation
  • D. When installing cables in plenum-rated air-handling spaces

Answer: C


NEW QUESTION # 38
If a horizontal cable is placed in an open ceiling return-air plenum, which cable rating is REQUIRED by NFPA and BICSI guidelines?

  • A. CMR
  • B. CM
  • C. CATVX
  • D. CMP

Answer: D


NEW QUESTION # 39
Which of the following steps should be performed first when an installer is pulling optical fiber cable?

  • A. Ensure the cable has been tested and accepted
  • B. Label cables
  • C. Attach pull rope
  • D. Install and secure innerduct

Answer: A


NEW QUESTION # 40
Which of the following fire-ratings provides information about smoke leakage?

  • A. L rating
  • B. E rating
  • C. W rating
  • D. I rating

Answer: A


NEW QUESTION # 41
Which of the following items may be used as a substitute device for a pulling eye?

  • A. Wire mesh grip
  • B. Fan-out kit
  • C. Innerduct
  • D. D rings

Answer: A


NEW QUESTION # 42
When performing an OTDR test on a multimode fiber, which of the following events indicates a likely macrobend?

  • A. A reflection at the far end with minimal insertion loss
  • B. A sudden spike with a large positive reflection
  • C. A gradual loss over the full distance of the fiber
  • D. A sharp drop in backscatter in a localized section of the trace

Answer: D


NEW QUESTION # 43
When bonding a shielded twisted-pair cable system, which of the following must be ensured to comply with proper grounding and bonding practices?

  • A. Only the outer jacket is stripped back to expose the shield at the connector
  • B. The cable shield is bonded to a non-conductive anchor to prevent ground loops
  • C. The shield is folded back outside of the connector for easy visual inspection
  • D. The drain wire or shield foil is securely bonded to the connecting hardware or patch panel that is connected to the TGB/TMGB

Answer: D


NEW QUESTION # 44
Which of the following is a benefit of air-blown optical fiber cable?

  • A. It is significantly cheaper than other types of cables
  • B. It requires less testing than other types of cables
  • C. It can be recovered and reused

Answer: C


NEW QUESTION # 45
What is the maximum permissible amount of untwisting for category 5e cable and higher?

  • A. 12.7 mm (0.5")
  • B. 75 mm (3")
  • C. 38 mm (1.5")
  • D. 25 mm (1")

Answer: A


NEW QUESTION # 46
......